{"affected":[{"defaultStatus":"unaffected","product":"AK-SM8xxA","source":"CNA: Danfoss","vendor":"Danfoss","versions":[{"lessThanOrEqual":"5.4.0","status":"affected","version":"0","versionType":"custom"}]}],"cveId":"CVE-2026-129713","cwes":["CWE-121"],"description":"A stack-based buffer overflow in an unauthenticated CGI handler of the\nDanfoss AK-SM 8xxA Series controller allows remote attackers to send specially\ncrafted HTTP/S POST requests, leading to memory corruption, webserver restart\nand hypothetically potential arbitrary code execution with webserver privileges.\nAuthentication is not required to exploit this vulnerability.","epss":{"date":"2026-11-23","percentile":0.62549,"score":0.00964},"exploits":[],"kev":null,"metrics":[{"score":9.3,"severity":"critical","source":"CNA: Danfoss","vector":"CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N","version":"4.0"},{"score":9.3,"severity":"critical","source":"NVD: d7ff35af-cf88-454c-bab9-af60602f10f8","vector":"CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X","version":"4.0"}],"modifiedAt":1795542607100,"publishedAt":1795171780291,"references":[{"source":"CNA: Danfoss","tags":[],"url":"https://www.danfoss.com/en/service-and-support/coordinated-vulnerability-disclosure/danfoss-security-advisories/dsa-2026-12-01/"},{"source":"d7ff35af-cf88-454c-bab9-af60602f10f8","tags":[],"url":"https://www.danfoss.com/en/service-and-support/coordinated-vulnerability-disclosure/danfoss-security-advisories/dsa-2026-12-01/"}],"remediation":[{"kind":"fix","source":"CNA: Danfoss","text":"*  This\n     vulnerability will be addressed in Danfoss AK-SM 8xxA Series upcoming software\n     version 5.5.x.\n\n   *  Further, we will\n     remove the option that customers can disable the product Strict mode."},{"kind":"workaround","source":"CNA: Danfoss","text":"*  Follow the\n     instructions provided in the product’s manual, avoiding Internet exposure\n     of all units on public IP\n\n   *  Make sure remote\n     access to the units is possible only through a secure VPN or in general\n     over a protected network\n\n   *  Configure the\n     units to Strict mode, which ensures higher security levels on the product\n\n   *  Recommend using strong passwords"}],"revision":"cf8a7fc71d4ef15b8b12bacf3c6271b0413df367c0104b13418a5c9868de5518","sources":[{"modifiedAt":1795171780291,"name":"CNA: Danfoss","retrievedAt":1795172909971,"url":"https://www.cve.org/CVERecord?id=CVE-2026-129713"},{"modifiedAt":1795542607100,"name":"NVD","retrievedAt":1795544237387,"url":"https://nvd.nist.gov/vuln/detail/CVE-2026-129713"},{"modifiedAt":null,"name":"FIRST EPSS","retrievedAt":1795501366039,"url":"https://api.first.org/data/v1/epss?cve=CVE-2026-129713"}],"ssvc":null,"status":"published","title":"Stack-based buffer overflow in Danfoss AK-SM8xxA unauthenticated CGI handler","updatedAt":1795544237387}